Conference Papers Database New search

Effect by Electrolysis for Dissolution and Precipitation of Calcite Scale in Cooling Water Line of Heat Exchange System

Norio Yanagisawa, Takahiro Matsumura

Key words
scale, calcite, electrolysis process, precipitation rate, dissolution rate, pH
Conference
New Zealand Geothermal Workshop
Year
2008
Session
Chemistry
Language
English

Full text

241KB, opens in a new tab

Abstract

A high-frequency electrolysis method was used to reduce the calcium in a circulating cooling water line by precipitating calcite on the electrodes. Therefore, this electrolysis system was useful to remove calcite scales in the flow line. In super-saturation solution for CaCO3, Ca and HCO3 concentration 100 mg/l solution, calcite scale on the stainless plate in the flow line dissolved with pH decreasing using electrolysis power supply. In contrast, no power supply, calcite precipitated more on stainless plate with pH slightly increasing.

When power supply, average dissolution rate was about 0.1 mg/m2/s and changed with pH decreased.

Copyright 2008, University of Auckland. Readers who download papers from this site should honour the copyright of the original authors, and may not copy or distribute the work further without the permission of the original publisher.

You have opened 0 records today from 216.73.216.139 (216.73.216.139).
Viewed 1 October 2026, 12:11 am.