Microbiological Induced Corrosion A Cited Case in Ohaaki Geothermal Power Station
- Conference
- PNOC-EDC Geothermal Conference
- Year
- 1997
- Session
- Process Chemistry
- Language
- English
Full text
367KB, opens in a new tab
Abstract
Most of the corrosion on the materials comprising the circulating water (CW] gcitea in Ohaaki are microbiologicallv induced. Sulfur, nitrogen and slime producing bacteria are recognised in the deterioration of the materials since they produced strong acids @.e. HSOJ during metabolism. The main defence wherein corrosion is controlled is by dosing a biocide in the circulating water, and coating the inner wall of the cooling tower which is ôout of the reach ÆÆ of biocide. A spray gun was installed in order to reach the vapour zone S wall with biocide treated circulating water. Therefore, the case of microbiologically induced corrosion cited in Ohaaki reduces the efficiency and qrraliQ of the materials making the CTY systeui, thus increases maintenance costs.
Copyright 1997, PNOC-EDC. Readers who download papers from this site should honour the copyright of the original authors, and may not copy or distribute the work further without the permission of the original publisher.