The research on heat pump performance which use the tail water of middle-deep geothermal heating
- Key words
- middle-deep geothermal; heat pump performance; geothermal heating; COP
- Conference
- World Geothermal Congress
- Year
- 2023
- Session
- Geothermal Heat Pumps
- Language
- English
- Paper number
- 515
Full text
0,91 MB, opens in a new tab
Abstract
In order to improve the COP of middle-deep geothermal heating system, the research was conducted to analysis the performance and COP of the heat pumps which use the geothermal tail water (10?~40?) after the cascade utilization of the middle-deep geothermal heating system as the heat source. The results show that:The COP of the high-temperature heat pump when the heat source inlet water temperature is 38? is increased by more than 40% compared with that of the ordinary heat pump when the heat source inlet water temperature is 18??Comparing the system COP of three different equipment configuration schemes of ordinary heat pump, high temperature heat pump + ordinary heat pump, two-stage high temperature heat pump + ordinary heat pump, it is concluded that the energy efficiency of the two-stage high temperature heat pump + ordinary heat pump is 20% higher than that of the ordinary heat pump system. The results may provide optimization recommendations for engineering design.
Copyright 2023, International Geothermal Association. Readers who download papers from this site should honour the copyright of the original authors, and may not copy or distribute the work further without the permission of the original publisher.