Conference Papers Database New search

OPTIMISATION OF CHEMICAL DOSING FOR TE MIHI COOLING TOWERS

M.G. Young

Key words
cooling water, microbiological control, glutaraldehyde, quaternary ammonium, caustic, sodium hydroxide, biocides, Sulphur oxidizing bacteria, geothermal
Conference
New Zealand Geothermal Workshop
Year
2018
Session
Session 1.2 Geothermal Engineering - Production and Manageme
Language
English
Paper number
103

Full text

546KB, opens in a new tab

Abstract

Te Mihi Uenukukopako (eew-new-koo-kor-par-kor) (Te Mihi) Power Station was commissioned in May 2014 but started experiencing cooling water pH control issues after 12 months operation. The alternating dual biocide programme of dosing a quaternary ammonium biodispersant/biocide (quat) one week then glutaraldehyde biocide (glut) the following week was no longer able to maintain control.
Alternative biocides were trialed to initially regain pH control, but it was then determined that the most cost and performance effective solution was to implement continuous caustic dosing, to compensate for the low concentration of ammonia in the steam and hence poor buffering ability to changes in pH, and to move to a less frequent, performance-based biocide dosing regime triggered by on-line conductivity monitoring and caustic consumption rate.
Te Mihi Power Station is a 2 x 83 MW double flash plant fed by the Wairakei geothermal field. Each unit has a c.4,400 m3 main cooling water system designed to withstand the corrosive environment associated with aerated geothermal fluid for a pH range of 4.5 to 8. Exposed materials are fiberglass, PVC, 316L stainless steel and epoxy-coated concrete.

Copyright 2018, University of Auckland. Readers who download papers from this site should honour the copyright of the original authors, and may not copy or distribute the work further without the permission of the original publisher.

You have opened 0 records today from 216.73.216.139 (216.73.216.139).
Viewed 26 September 2026, 6:39 am.