Development of Ground-Source Heat Pump System Using a Flowing Well
- Key words
- ground-source heat pump system, flowing well, performance, Japan
- Location
- Japan
- Conference
- Asian Geothermal Symposium
- Year
- 2016
- Language
- English
Full text
1MB, opens in a new tab
Abstract
For the promotion of ground-source heat pump (GSHP) system in Japan, development of highly efficient system is essential. In this study, GSHP system was developed using a flowing well as a ground heat exchanger (GHE). Flowing well of 250mm diameter and 100m depth was constructed. Slit screens were set at intervals of 61.45 m - 83.45 m and 88.95 m - 99.95 m. 3 sets of 100m double U-tube with 34mm external diameter were installed and connected to 3 heat pumps of 10kW capacity. Performance of the system was evaluated for space-heating and space-cooling of an office building with room area of 126.7 sq. m. Average coefficient of performance (COP) was 4.5 for space-heating and 8.1 for space-cooling. Maximum heat exchange rate was 70.8 W/m for space-heating and 57.6 W/m for space-cooling. It can be said from these data that the system resulted in higher performance. Energy saving and cost reduction can be expected from this kind of system.
Copyright 2016, Asian Geothermal Symposium. Readers who download papers from this site should honour the copyright of the original authors, and may not copy or distribute the work further without the permission of the original publisher.