Long-term Performance of a Borehole Heat Exchanger Field Connected to a Multifunctional Office Building

Michalski, A; Fütterer, J; Volkmann, J; Mottarghy, D; Klitzsch, N; Clauser, C

Key words
borehole heat exchanger, BHE, geothermal energy, numerical modelling, sustainability
Conference
European Geothermal Congress
Year
2016
Session
Technology and Best practice – Heat Pumps
Language
English
Paper number
T-HP-227

Full text

632KB, opens in a new tab

Abstract

We present results of long-term numerical simulations of a large array of borehole heat exchangers (BHE) serving a multifunctional building. Automatically controlled heating and cooling operation has been monitored for a period of over two years. This data set, including groundwater flow, was used for a numerical simulation of the subsurface temperature over a period of ten years. Data from distributed optical temperature sensing (DTS) was used in some of the boreholes for calibrating the simulation results. We see different behaviours of BHEs depending on their specific position. We used the results on the variation of sub-surface temperature with time for optimizing the building’s control regarding the management of the heating and cooling operation mode . With all monitoring and measuring systems in place at the E.ON ERC multifunctional building, the BHE array provides ideal ground-truth for testing long-term numerical simulations for a sustainable and cost reducing operation of such buildings..

Copyright 2016, EGEC / EGC2016. Readers who download papers from this site should honour the copyright of the original authors, and may not copy or distribute the work further without the permission of the original publisher.

You have opened 0 records today from 216.73.217.142 (216.73.217.142).
Viewed 21 September 2026, 4:14 pm.